CLS200 Series User’s Guide
Chapter 6: Ramp/Soak
121
Segment Setpoint
Enter the ending setpoint for the segment you are editing. For a ramp, the setpoint changes steadily
over the segment time from the end setpoint of the previous segment to the value set here. For a
soak, set the value here equal to the end setpoint of the previous segment.
ALARM
C SEGMENT 5
SEG SETPT? OFF
Selectable values: -999 to 3276, or OFF (no output during segment). See Setpoints and
Tolerances for Various Input Types on page 124.
Edit Segment Events
You can assign up to four digital outputs, or events, to each segment. When the segment ends, the
outputs you select are set to the state you specify. Press YES to select outputs and specify their
states.
ALARM
A SEGMENT 5
EDIT SEG EVENTS?
Press NO to advance to the EDIT SEG TRGGRS parameter.
NOTE! Events are set at the end of segments. If you want a segment to start with an
event, program the event in the previous segment. You can also create a segment with
zero time preceding the segment during which you want the event on.
Segment Event Output
Select a digital output for the event. Use a digital output that is not being used for PID control or for
Serial DAC clock.
This parameter appears only if you answered YES to EDIT SEG EVENTS?
ALARM
A READY EVENT
OUTPUT 15? OFF
Selectable values: Any digital output from 1 to 34, except those in use, or NONE (no event).
When you are done setting segment events, press BACK to return to EDIT SEG EVENTS, then
press NO to go to the next parameter.