Selectable values: NONE, or any output from 1 to 34 not enabled for closed-loop control or for the
Serial DAC clock.
Deviation Alarm Value
Set the deviation from setpoint at which the high and low deviation alarms occur.
ALARM
01 DEV ALARM
VALUE ? 5
Selectable values: 0 to 255, 25.5, 2.55, .255 or .0255, depending on the INPUT TYPE and
DISP FORMAT settings.
High Deviation Alarm Type
Select an alarm type for the high deviation alarm.
ALARM
01 HI DEV ALARM
TYPE ? OFF
Selectable values: ALARM, CONTROL or OFF.
High Deviation Alarm Output Number
Choose a digital output to activate when the high deviation alarm occurs, if desired.
ALARM
01 HI DEV ALARM
OUTPUT ? NONE
Selectable values: NONE, or any output from 1 to 34 not enabled for closed-loop control or for the
Serial DAC clock.
Low Deviation Alarm Type
Select an alarm type for the low deviation alarm.
ALARM
01 HI DEV ALARM
TYPE ? OFF
Selectable values: ALARM, CONTROL or OFF.