Chapter 6: Ramp/Soak
128
3. Press the NO key. You will see the RESET PROFILE parameter. See Resetting a Profile on
page 130.
4. Press YES then ENTER to reset the profile. You will see the ASSIGN PROFILE parameter.
See Assigning a Profile to a Loop on page 127.
5. Choose one of the available profiles or NONE (to unassign) and press ENTER.
6. To return to the single loop display without changing the profile assignments, press BACK.
Running a Profile
When you assign a profile, it does not start running immediately. Instead, the loop is in the START
mode and the READY segment (segment 0). Use the SET MODE parameter to start a profile (put it in
RUN mode).
ALARM
01 ASSIGN R/S
PROFILE? A
Starting a Profile
You can start a profile only when it is in the READY segment.
1. In the single loop display, switch to the loop you want to start.
2. Press the RAMP/SOAK key three times. The SET MODE parameter appears.
3. Press YES and ENTER to start the profile. While the profile is in START mode, the only mode
available is the RUN mode.
Running Several Profiles Simultaneously
To run several profiles simultaneously, follow these steps:
1. Set up the profiles so that segment 1 of each profile has the same latched trigger.
2. Assign the profiles to the appropriate loops. The loops will go to the READY segment of
each profile.
3. Set each profile to RUN mode.
4. Trip the trigger.
Editing a Profile While It Is Running
You can edit a profile while it is running. Changes made to segments after the current segment will
take effect when the segment is reached. Changes made to the segments that have already been
completed will take effect the next time the profile is run. Do not edit the current segment. Changes
to the current segment can have unexpected consequences.
Holding a Profile or Continuing from Hold
Use the SET MODE parameter to select the ramp/soak profile mode. Table 6.6 shows the
available modes.