Table 2.10 EIA/TIA-232 Connections
WIRE COLOR CLS200 TB1 DB 9 CONNECTOR DB 25 CONNECTOR
White TX Pin 26 RX Pin 2 RX Pin 3
Red RX Pin 25 TX Pin 3 TX Pin 2
Black GND Pin 23 GND Pin 5 GND Pin 7
Green GND Pin 24 N/U Pin 9 N/U Pin 22
Shield N/C GND Pin 5 GND Pin 7
Jumpers in EIA/TIA-232 Connectors
Some software programs and some operator interface terminals require a Clear to Send (CTS) signal
in response to their Request to Send (RTS) signal, or a Data Set Ready (DSR) in response to their
Data Terminal Ready (DTR). The CLS200 is not configured to receive or transmit these signals. To
use such software with the CLS200, jumper the RTS to the CTS and the DTR to the DSR in the DB
connector. Table 2.11 lists the standard pin assignments for DB-9 and DB-25 connectors.
Table 2.11RTS/CTS Pins in DB-9 and DB-25 Connectors
DB-9 DB-25
RTS 7 4
CTS 8 5
DTR 4 20
DSR 6 6
Cables manufactured by Watlow for EIA/TIA-232 communications include these jumpers.
WATLOW ANAFAZE CLS200
LOOP
PROCESS
UNITS
ALARM
SETPOINT
STATUS
OUT%
MAN
AUTO
CHNG
SP
A
L
A
R
M
A
C
K
RAMP
SOAK
YES
N
O
BACK
E
NTE
R
EIA/TIA-232
cable
Figure 2.25 Connecting One CLS200 to a Computer Using EIA/TIA-232