CLS200 Series User’s Guide
Chapter 4: Setup
76
Loop Name
Assign a two-character name to the loop. This name is shown on the single loop display in place of
the loop number.
ALARM
01 LOOP
NAME ? 01
Selectable values: 0 to 9, A to Z, %, /, ° (degree symbol).
Input Units
For loops with temperature sensor input types, choose a temperature scale: Fahrenheit or Celsius.
For a linear or pulse loop, choose a three-character description of the loop’s engineering units.
ALARM
01 INPUT
UNITS ?
˚F
Selectable values: The table below shows the character set for input units.
Table 4.7Input Character Sets
INPUT CHARACTER SETS FOR UNITS
Thermocouple or RTD ˚ F or ˚ C
LINEAR or PULSE 0 to 9, A to Z,%, /, °, space
Input Reading Offset
If the input type is a thermocouple or RTD, specify the offset to correct for signal inaccuracy at a
given point. For example, at temperatures below 400°F, a type J thermocouple may be inaccurate or
“offset” by several degrees. Use an independent thermocouple or your own calibration equipment to
find the offset for your equipment.
A positive value increases the reading and a negative value decreases it.
ALARM
01 INPUT READING
OFFSET ? 0˚F
Selectable values: See Table 4.8.