CLS200 Series User’s Guide
Chapter 2: Installation
35
CH IN+
CH IN-
Device with
Voltage
Output
CH IN+
Device with
Voltage
Output
Sixteen-Loop Controller
Four-Loop or Eight-Loop Controller
Com
Figure 2.15 Linear Voltage Signal Connections
Current Input Connections
This input type requires scaling resistors. Special input resistors installed at Watlow for analog
current signals are such that the controller sees a -10 to 60mV signal across its inputs for the loop.
CH IN+
CH IN-
Device with
Current
Output
CH IN+
Com/Ref Com
Device with
Current
Output
Sixteen-Loop Controller
Four-Loop or Eight-Loop Controller
Figure 2.16 Linear Current Signal Connections
NOTE! When mixing current inputs with low-voltage inputs (thermocouples or voltage
inputs less than 1V) to a sixteen-loop controller, connect the current inputs to the IN+
and Ref Com terminals. If no low-voltage sensors are used, connect current inputs to the
IN+ and Com terminals on TB1.
Pulse Input Connections
The CLS200 can accept a pulse input of up to 2000Hz from a device such as an encoder. The
frequency of this input is scaled with user-set parameters. See Setup Loop Input Menu on page
74 and Example 3: A Pulse Encoder on page 161. This scaled value is the process variable for
loop 5 on a four-loop model, loop 9 on an eight-loop model or loop 17 on a sixteen-loop model.
The CLS200 can accommodate encoder signals up to 24VDC using a voltage divider or can
power encoders with the 5VDC from the TB50 or TB18. The following figures illustrate connecting
encoders. A pull-up resistor in the CLS200 allows open collector inputs to be used.