CLS200 Series User’s Guide
Chapter 4: Setup
90
Table 4.13Setup Loop Alarms
PARAMETER DEFAULT VALUE
HI PROC ALARM SETPT? 1000
HI PROC ALARM TYPE? OFF
HI PROC ALARM OUTPUT? NONE
DEV ALARM VALUE? 5
HI DEV ALARM TYPE? OFF
HI DEV ALARM OUTPUT? NONE
LO DEV ALARM TYPE? OFF
LO DEV ALARM OUTPUT? NONE
LO PROC ALARM SETPT? O
LO PROC ALARM TYPE? OFF
LO PROC ALARM OUTPUT? NONE
ALARM DEADBAND? 2
ALARM DELAY? O SECONDS
High Process Alarm Setpoint
Set the value at which the high process alarm activates.
ALARM
01 HI PROC ALARM
SETPT ? 1000
Selectable values: Any point within the scaled sensor range.
High Process Alarm Type
Select an alarm type for the high process alarm.
ALARM
01 HI PROC ALARM
TYPE ? OFF
Selectable values: OFF, ALARM, or CONTROL.
High Process Alarm Output Number
Choose a digital output to activate when the high process alarm occurs, if desired.
ALARM
01 HI PROC ALARM
OUTPUT? NONE