CLS200 Series User’s Guide
Chapter 6: Ramp/Soak
127
Cycle Number Display
From the single loop display, press the RAMP/SOAK key twice. This screen displays the number of
times the profile has run out of the total number of cycles. In this example, the ramp/soak profile is
on the 10th of 15 cycles to be performed.
ALARM
04 A SEG10/20 R
CYCLE NR= 10/15
Set Mode Display
From the single loop display, press the RAMP/SOAK key three times. The SET MODE parameter
allows you to change the ramp/soak mode.
ALARM
01 A SEG01/05 R
SET MODE? START
See Running a Profile on page 128 and Holding a Profile or Continuing from Hold on page 128 for
instructions on changing the ramp/soak mode.
Assigning a Profile to a Loop
Use this parameter to assign a profile to a loop.
ALARM
01 ASSIGN R/S
PROFILE? A
Selectable Values: A to Q or NONE
Assigning a Profile the First Time
To assign a profile to a loop that does not have a profile currently assigned:
1. In the single loop display, switch to the loop you want to assign a profile to.
2. Press the RAMP/SOAK key. The ASSIGN R/S PROFILE parameter appears.
3. Choose one of the available profiles and press ENTER
- or -
press BACK to return to single loop display without sending profile data to the controller.
Assigning, Changing and Unassigning a Profile
To assign a new profile to a loop that already has one assigned:
1. In the single loop display, switch to the loop in which you want to change or unassign
the profile.
2. Press the RAMP/SOAK key three times.