TECHNICALSPECIFICATIONS
Table8.6:Current,powerandlossdataforB2andT2linesand“HD”overloadclass
HDoverloadclass:
150%for60secondswitha5-minuteinterval
200%for3secondswitha5-minuteinterval
Inverterlossdataas
perIEC61800-9-2
(1)
Invertermodel
Typicalmotor
(2)
Dissipatedpower
forsizingthe
panel
Rated
apparent
power
Rated
output
current
220V/60Hz230V/50Hz230V/60Hz
NEC
Table
208V
NEC
Table
230V
Inverter
complete
Front
part
230V
Lossesat
ratedcondition
/
Apparentpower
Io,nom(HD)P,nomP,nomP,nomP,nomP,nomPL(inv)PL(inv2)SopL(90,100)
[Arms][CV][kW][hp][hp][hp][W][W][kVA][%]
CFW900A04P6B24.61.51.11.51181341.84.4%
CFW900A06P0B2621.5211.596392.44.1%
CFW900A07P5B27.521.52221094133.7%
CFW900A10P0B21032.23231274643.2%
CFW900A04P6T24.61.51.11.51170301.83.9%
CFW900A06P0T251.51.5211733123.7%
CFW900A07P5T26.821.521.5285332.73.2%
CFW900A10P6T29.632.2323102353.82.7%
CFW900A13P0T21133333111374.42.6%
CFW900A19P0T21654535143426.32.3%
CFW900B26P0T2227.55.57.557.5212598.72.5%
CFW900B34P0T228107.5107.5102606711.12.4%
CFW900B45P0T23512.59.21010103207613.92.3%
CFW900C56P0T247151115151544710318.72.4%
CFW900C70P0T259201525152052311523.52.3%
CFW900C80P0T2702518.530202561412927.92.2%
CFW900D0110T292302230303078414836.62.2%
CFW900D0135T2110403040304094217243.82.2%
CFW900D0150T21245037504040108119249.42.2%
CFW900E0172T21506045605050139126759.72.4%
CFW900E0195T21606045605060149728163.72.4%
CFW900E0250T221175557575751934342842.4%
(1)
ThedissipatedpowerforsizingthepanelmustbeconsideredthesamespecifiedfortheNDoverloadclassaccordingto
Table8.5.
(2)
RatedpowervaluesdefinedbasedontheratedcurrentofWEGmotorsattheindicatedvoltages.
Item8.1.4indicatesthemaximuminverter
ambienttemperatureconsideredforchoosingthemotor.
CFW900|99