TECHNICALSPECIFICATIONS
Table8.7:Current,powerandlossdataforT4lineand“ND”overloadclass
NDoverloadclass:
110%for60secondswitha5-minuteinterval
150%for3secondswitha5-minuteinterval
Inverterlossdataas
perIEC61800-9-2
(1)
Invertermodel
Typicalmotor
(2)
Dissipatedpower
forsizingthe
panel
Rated
apparent
power
Rated
output
current
380V/60Hz400V/50Hz440V/60Hz460V/60Hz
NEC
Table
460V
Inverter
complete
Front
part
400V
Lossesat
ratedcondition
/
Apparentpower
Io,nom(ND)P,nomP,nomP,nomP,nomP,nomPL(inv)PL(inv2)SopL(90,100)
[Arms][CV][kW][hp][hp][hp][W][W][kVA][%]
CFW900A02P8T42.81.51.11.52166301.93.5%
CFW900A03P6T43.621.522272312.52.9%
CFW900A04P8T44.832.233390333.32.7%
CFW900A06P5T46.533454110364.52.5%
CFW900A09P6T49.66467.55145426.72.2%
CFW900A14P0T4147.57.5101010201489.72.1%
CFW900A17P0T417107.512.510102365411.82.0%
CFW900B26P0T42615112020153668218.02.1%
CFW900B33P0T43320152525204098722.91.8%
CFW900B39P0T4392518.53030254739727.01.8%
CFW900C50P0T450302240403067113334.62.0%
CFW900C62P0T462403050504072714343.01.7%
CFW900C74P0T474503760605084416151.31.7%
CFW900D96P0T4966045757575113219566.51.8%
CFW900D0124T41247555100100100140823385.91.7%
CFW900D0146T4146100751251251001656271101.21.7%
CFW900E0172T4172125901251501251789333119.21.6%
CFW900E0203T42031501101501751502170384140.61.6%
CFW900E0242T42421751322002002002504428167.71.5%
(1)
Inverterefficiencyrating: see
item8.1.1.InverterlossesattheothersevenoperatingpointsspecifiedbyIEC61800-9-2standard:see
specificdocumentonEcodesignDirective.Todeterminelossesfordifferentmotors,usetheWEGEcodriveapp.
(2)
RatedpowervaluesdefinedbasedontheratedcurrentofWEGmotorsattheindicatedvoltages.
Item8.1.4indicatesthemaximuminverter
ambienttemperatureconsideredforchoosingthemotor.