TROUBLESHOOTINGANDMAINTENANCE
Protection/AlarmDescriptionPossiblecauses
F1117:
SlotAAI3cable
disconnection
Analoginputsignalsettoactualmodeisoutofthe
range4to20mA.
-AIcablebroken(thereadvaluewaslessthan2mA
for5seconds).
Poorcontactonthesignalconnectionatthe
terminals.
A1118:
SlotAAI4cable
disconnection
Analoginputsignalsettoactualmodeisoutofthe
range4to20mA.
-AIcablebroken(thereadvaluewaslessthan2mA
for5seconds).
Poorcontactonthesignalconnectionatthe
terminals.
F1119:
SlotAAI4cable
disconnection
Analoginputsignalsettoactualmodeisoutofthe
range4to20mA.
-AIcablebroken(thereadvaluewaslessthan2mA
for5seconds).
Poorcontactonthesignalconnectionatthe
terminals.
F1125:
SlotAtemp.sensor
wronghwconfig.
SensortypeselectedbytheaccessoryDIPswitches
otherthanthesensortypeconfiguredbythe
parameters.
- DIPswitch configured incorrectly.Checkthe
CFW900-TEMP-01accessoryguide.
-”Sensor Type”parameterincorrectlyconfigured.
CheckthedescriptioninC5.2.6.1.
A1126:
SlotAtemperature
sensor1error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1127:
SlotAtemperature
sensor1error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1128:
SlotAhightemperature
insensor1
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1129:
SlotAsensor1
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1130:
SlotAtemperature
sensor2error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1131:
SlotAtemperature
sensor2error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1132:
SlotAhightemperature
insensor2
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1133:
SlotAsensor2
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1134:
SlotAtemperature
sensor3error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1135:
SlotAtemperature
sensor3error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1136:
SlotAhightemperature
insensor3
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
CFW900|69