English
TROUBLESHOOTINGANDMAINTENANCE
Protection/AlarmDescriptionPossiblecauses
F1137:
SlotAsensor3
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1138:
SlotAtemperature
sensor4error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1139:
SlotAtemperature
sensor4error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1140:
SlotAhightemperature
insensor4
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1141:
SlotAsensor4
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1142:
SlotAtemperature
sensor5error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1143:
SlotAtemperature
sensor5error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1144:
SlotAhightemperature
insensor5
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1145:
SlotAsensor5
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1146:
SlotAtemperature
sensor6error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1147:
SlotAtemperature
sensor6error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1148:
SlotAhightemperature
insensor6
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1149:
SlotAsensor6
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1200:
SlotBincompatible
accessory
Errorduringaccessoryfirmwareupdate.Oldinverterfirmwareversion.
F1201:
SlotBInitializationError
Itwasnotpossibletoinitializearesourcerequiredfor
theaccessorytowork.
-Resourcealreadyinusebyanotheraccessory.
Inthecaseofcommunicationnetworkaccessories,
onlyoneaccessoryofeachtypeofnetworkcanbe
connectedtotheinverteratatime.
F1203:
SlotBaccessory
connection
Lossofcommunicationwiththeaccessory.-Above-supportedelectromagneticnoise.
-Vibrationabovesupportedlimitscausingconnector
problems.
-Corruptedaccessoryfirmware.
70|CFW900