TROUBLESHOOTINGANDMAINTENANCE
Protection/AlarmDescriptionPossiblecauses
F1217:
SlotBAI3cable
disconnection
Analoginputsignalsettoactualmodeisoutofthe
range4to20mA.
-AIcablebroken(thereadvaluewaslessthan2mA
for5seconds).
Poorcontactonthesignalconnectionatthe
terminals.
A1218:
SlotBAI4cable
disconnection
Analoginputsignalsettoactualmodeisoutofthe
range4to20mA.
-AIcablebroken(thereadvaluewaslessthan2mA
for5seconds).
Poorcontactonthesignalconnectionatthe
terminals.
F1219:
SlotBAI4cable
disconnection
Analoginputsignalsettoactualmodeisoutofthe
range4to20mA.
-AIcablebroken(thereadvaluewaslessthan2mA
for5seconds).
Poorcontactonthesignalconnectionatthe
terminals.
F1225:
SlotBtemp.sensor
wronghwconfig.
SensortypeselectedbytheaccessoryDIPswitches
otherthanthesensortypeconfiguredbythe
parameters.
- DIPswitch configured incorrectly.Checkthe
CFW900-TEMP-01accessoryguide.
-”Sensor Type”parameterincorrectlyconfigured.
CheckthedescriptioninC5.2.6.1.
A1226:
SlotBtemperature
sensor1error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1227:
SlotBtemperature
sensor1error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1228:
SlotBhightemperature
insensor1
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1229:
SlotBsensor1
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1230:
SlotBtemperature
sensor2error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1231:
SlotBtemperature
sensor2error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1232:
SlotBhightemperature
insensor2
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1233:
SlotBsensor2
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1234:
SlotBtemperature
sensor3error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1235:
SlotBtemperature
sensor3error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1236:
SlotBhightemperature
insensor3
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
72|CFW900