TROUBLESHOOTINGANDMAINTENANCE
Protection/AlarmDescriptionPossiblecauses
F1237:
SlotBsensor3
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1238:
SlotBtemperature
sensor4error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1239:
SlotBtemperature
sensor4error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1240:
SlotBhightemperature
insensor4
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1241:
SlotBsensor4
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1242:
SlotBtemperature
sensor5error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1243:
SlotBtemperature
sensor5error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1244:
SlotBhightemperature
insensor5
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1245:
SlotBsensor5
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1246:
SlotBtemperature
sensor6error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1247:
SlotBtemperature
sensor6error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1248:
SlotBhightemperature
insensor6
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1249:
SlotBsensor6
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1300:
SlotCincompatible
accessory
Errorduringaccessoryfirmwareupdate.Oldinverterfirmwareversion.
F1301:
SlotCInitializationError
Itwasnotpossibletoinitializearesourcerequiredfor
theaccessorytowork.
-Resourcealreadyinusebyanotheraccessory.
Inthecaseofcommunicationnetworkaccessories,
onlyoneaccessoryofeachtypeofnetworkcanbe
connectedtotheinverteratatime.
F1303:
SlotCaccessory
connection
Lossofcommunicationwiththeaccessory.-Above-supportedelectromagneticnoise.
-Vibrationabovesupportedlimitscausingconnector
problems.
-Corruptedaccessoryfirmware.