TROUBLESHOOTINGANDMAINTENANCE
Protection/AlarmDescriptionPossiblecauses
F1717:
SlotGAI3cable
disconnection
Analoginputsignalsettoactualmodeisoutofthe
range4to20mA.
-AIcablebroken(thereadvaluewaslessthan2mA
for5seconds).
Poorcontactonthesignalconnectionatthe
terminals.
A1718:
SlotGAI4cable
disconnection
Analoginputsignalsettoactualmodeisoutofthe
range4to20mA.
-AIcablebroken(thereadvaluewaslessthan2mA
for5seconds).
Poorcontactonthesignalconnectionatthe
terminals.
F1719:
SlotGAI4cable
disconnection
Analoginputsignalsettoactualmodeisoutofthe
range4to20mA.
-AIcablebroken(thereadvaluewaslessthan2mA
for5seconds).
Poorcontactonthesignalconnectionatthe
terminals.
F1725:
SlotGtemp.sensor
wronghwconfig.
SensortypeselectedbytheaccessoryDIPswitches
otherthanthesensortypeconfiguredbythe
parameters.
- DIPswitch configured incorrectly.Checkthe
CFW900-TEMP-01accessoryguide.
-”Sensor Type”parameterincorrectlyconfigured.
CheckthedescriptioninC5.2.6.1.
A1726:
SlotGtemperature
sensor1error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1727:
SlotGtemperature
sensor1error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1728:
SlotGhightemperature
insensor1
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1729:
SlotGsensor1
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1730:
SlotGtemperature
sensor2error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1731:
SlotGtemperature
sensor2error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1732:
SlotGhightemperature
insensor2
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1733:
SlotGsensor2
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1734:
SlotGtemperature
sensor3error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1735:
SlotGtemperature
sensor3error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1736:
SlotGhightemperature
insensor3
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.