TROUBLESHOOTINGANDMAINTENANCE
Protection/AlarmDescriptionPossiblecauses
F1737:
SlotGsensor3
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1738:
SlotGtemperature
sensor4error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1739:
SlotGtemperature
sensor4error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1740:
SlotGhightemperature
insensor4
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1741:
SlotGsensor4
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1742:
SlotGtemperature
sensor5error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1743:
SlotGtemperature
sensor5error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1744:
SlotGhightemperature
insensor5
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1745:
SlotGsensor5
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
A1746:
SlotGtemperature
sensor6error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
F1747:
SlotGtemperature
sensor6error
Valuemeasuredbythetemperaturesensoroutofthe
expectedrange.
-Sensorcableisbroken.
-Short-circuitedsensor.
-Sensorlocatedinanextremelylowtemperature
environment.
A1748:
SlotGhightemperature
insensor6
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.
F1749:
SlotGsensor6
overtemperature
Temperaturemeasuredbythesensorclosetothe
thresholdlevel.
-Monitoredequipmentatahightemperature.
-Faultactuationlevelconfigurationerror.