Manual 37365A GCP-30 Series Packages - Genset Control
Page 154/179 © Woodward
MUX
No.
Contents (words)
Unit Note
3/2 11
Actual mains interchange (import/export)
real power
W × 10
PNTEXPO
3/3 12
Control register 1
Bit 15 = 1 \
Bit 14 = 1 /
Starting enabled (in isolated operation or
mains parallel operation)
Note – On double /fourfold bits the follow-
ing is valid: If the indicated bit combination
is fulfilled (
high byte and low byte) ,the
message is active (otherwise inactive).
Bit 13 = 1 \
Bit 12 = 1 /
--Internal--
Bit 11 = 1 \
Bit 10 = 1 /
Execution of acknowledgment
of a class F2/F3 alarm
Bit 9 = 1 \
Bit 8 = 1 /
Execution of acknowledgment
of a class F1 alarm
Bit 7 = 1 \
Bit 6 = 1 /
--Internal--
Bit 5 = 1 \ State of generator busbar 1 = OK
Bit 4 = 1 / --Internal--
Bit 3 = 1 \
Bit 2 = 1 /
--Internal--
Bit 1 = 1 \
Bit 0 = 0 /
--Internal--
4/1 13
Alarm message IKD (SC10) Bit 15 = 1 Failure DI8 of the IKD1.1
Note – On double /fourfold bits the follow-
ing is valid: If the indicated bit combination
is fulfilled (
high byte and low byte) ,the
message is active (otherwise inactive).
Bit 14 = 1 Failure DI7 of the IKD1.1
Bit 13 = 1 Failure DI6 of the IKD1.1
Bit 12 = 1 Failure DI5 of the IKD1.1
Bit 11 = 1 Failure DI4 of the IKD1.1
Bit 10 = 1 Failure DI3 of the IKD1.1
Bit 9 = 1 Failure DI2 of the IKD1.1
Bit 8 = 1 Failure DI1 of the IKD1.1
Bit 7 = 1 --Internal--
Bit 6 = 1 --Internal--
Bit 5 = 1 --Internal--
Bit 4 = 1 --Internal--
Bit 3 = 1 --Internal--
Bit 2 = 1 --Internal--
Bit 1 = 1 --Internal--
Bit 0 = 1 --Internal--
4/2 14
Internal alarm 6 Bit 15 = 1 MPU plausibility fault
Note – On double /fourfold bits the follow-
ing is valid: If the indicated bit combination
is fulfilled (
high byte and low byte) ,the
message is active (otherwise inactive).
Bit 14 = 1 Engine shutdown malfunction
Bit 13 = 1 Time overrun, GCB dead bus switching
Bit 12 = 1 --Internal--
Bit 11 = 1 MCB open switch malfunction
Bit 10 = 1 GCB open switch malfunction
Bit 9 = 1 MCB synchronization time monitoring
Bit 8 = 1 GCB synchronization time monitoring
Bit 7 = 1 Range alarm analog input [T8]
Bit 6 = 1 Range alarm analog input [T7]
Bit 5 = 1 Range alarm analog input [T6]
Bit 4 = 1 Range alarm analog input [T5]
Bit 3 = 1 Range alarm analog input [T4]
Bit 2 = 1 Range alarm analog input [T3]
Bit 1 = 1 Range alarm analog input [T2]
Bit 0 = 1 Range alarm analog input [T1]
4/3 15
Generator voltage delta V
23
V × 10
UGNEXPO
5/1 16
Generator voltage delta V
31
V × 10
UGNEXPO
5/2 17
Generator voltage wye V
1N
V × 10
UGNEXPO
5/3 18
Generator voltage wye V
2N
V × 10
UGNEXPO
6/1 19
Generator voltage wye V
3N
V × 10
UGNEXPO