Manual 37365A GCP-30 Series Packages - Genset Control
Page 32/179 © Woodward
Password Configuration
NOTE
Once the code level is entered, access to the configuration menus will be allowed for two hours or until
another password is entered into the control. If a user needs to exit a code level, then the control
should have the CS0 code level enabled. This will block access to all of the control’s parameters. A us-
er may re-enable the CS0 code level by changing any one digit of the randomly generated number on
the password screen and entering it into the unit.
The control unit automatically reverts to code level CS0 two hours after the entry of a password, or if
the power supply is disconnected from the control unit. By entering the correct password, the corres-
ponding level may again be accessed.
Parameter 32
Define level 1
code 0000
Code level 1 (Customer) 0000 to 9999
Access to this parameter is only enabled when the CS2 access code has been en-
tered into the controller. Personnel assigned the CS1 password will be permitted
access only to select parameters.
The default access code for this code level (CS) is CS1 = 0 0 0 1
Parameter 33
Define level 2
code 0000
Code level 2 (Commissioner) 0000 to 9999
Access to this parameter is only enabled when the CS2 access code has been en-
tered into the controller. Personnel assigned the CS2 password will be permitted
access to all parameters.
The default access code for this code level (CS) is CS2 = 0 0 0 2