Manual 37365A GCP-30 Series Packages - Genset Control
© Woodward Page 69/179
Synchronization
Synchronization of the GCB
GCB synchronization will be performed with frequency and voltage correction when the following conditions
have been met:
NOTE
The GCP-30series controller does not have maximum phase angle limit for synchronization. The GCP-
30 uses the parameters "Closing time GCB" (Parameter 120) and/or "Closing time MCB" (Para-
meter 121) to
calculates the optimum time for a breaker closure signal to be issued with the measured
frequency differential. The typical maximum tolerances are 1.5° to 3.5° with a frequency differential
ranging of 0.2 Hertz to 0.49 hertz. If the parameters "Closing time GCB" and/or "Closing time MCB" are
not configured accurately, these tolerances will increase due to inaccurate information being provided
for the close command calculation resulting in a larger phase angle at closing.
Automatic mode
The control has been placed in the AUTOMATIC operation mode
The circuit breaker logic (Parameter 111) is configured as "PARALLEL" (m
ains parallel operation), "IN-
TERCHANGE" (mains interchange (import/export) real power control), or "CLOSED TRANSIT." (make-
before-break/overlap synchronization)
An F2 or F3 class alarm has not been detected
The "Automatic 1" (terminal 3) or "Automatic 2" (terminal 5) discrete input has been energized, a remote
starting signal has be activated via the interface, or an emergency power operation has been initiated resulting
in additional engines being started
The busbar is energized (the control measures voltage on the bus)
The engine is running and the generator voltage and frequency are within the permissible limits
The delayed engine monitoring (Parameter 271) has expired (this does not apply in the case of emergency
power)
The rotating field of the generator and the mains voltages are identical and no alarms are displayed
Manual mode
The control has been placed in the MANUAL operation mode
The circuit breaker logic (Parameter 111) is configured as "PARALLEL" (m
ains parallel operation), "IN-
TERCHANGE" (mains interchange (import/export) real power control), or "CLOSED TRANSIT." (make-
before-break/overlap synchronization)
An F2 or F3 class alarm has not been detected
The busbar is energized (the control measures voltage on the bus)
The engine is running and the generator voltage and frequency are within the permissible limits
The "GCB ON" push-button has been pressed
The rotating field of the generator and the mains voltages are identical and no alarms are displayed
Load test mode
The control has been placed in the MANUAL operation mode
The circuit breaker logic (Parameter 111) is configured as "PARALLEL" (m
ains parallel operation), "IN-
TERCHANGE" (mains interchange (import/export) real power control), or "CLOSED TRANSIT." (make-
before-break/overlap synchronization)
An F2 or F3 class alarm has not been detected
The busbar is energized (the control measures voltage on the bus)
The engine is running and the generator voltage and frequency are within the permissible limits
The "GCB ON" push-button has been pressed
The rotating field of the generator and the mains voltages are identical and no alarms are displayed