EasyManua.ls Logo

Xinje VH6 Series - Group AD AIAO Correction Parameters

Xinje VH6 Series
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
167
Decelerate and stop function. VB5N : assign 7 to H2000,
VH6 : assign 5 to H1100.
Turning on the mapping function can only modify the corresponding address, but cannot modify the content in
the address. If the value is set in the program, writing 7 to H1100 means “fault reset”, and the program still
needs to be modified under this condition.
Specific instructions are as follows:
When the A9-00 is set to 1, the communication mapping function is enabled, and the data can only be read and
written through the mapping address set in A9-01~A9-14. If the communication address in the data frame is
inconsistent with the address value set in A9-01~A9-14, the inverter reply frame will report the communication
address error, resulting in alarm of normal communication control.
For example, the original control system needs to start and stop (forward rotation) through communication and
given frequency. Use VH6 replace VB5N, the frequency address is 0x2000, and the start and stop control
address is 0x2001. A9-00 is set to 1, A9-01 is set to 0x2000, A9-02 is set to 0x2001, A9-15 is set to 0x1000 ,
and A9-16 is set to 0x1100.
Write 50.00Hz data frame: 01 06 20 00 27 10 97 36
Start / Stop data frame: 01 06 20 01 00 01 12 0A
4-2-22. Group AD AIAO correction parameters
Parameter
Name
Range
AD-00
AI1 measured voltage 1
0.500V~4.000V
AD-01
AI1 display voltage 1
0.500V~4.000V
AD-02
AI1 measured voltage 2
6.000V~9.999V
AD-03
AI1 display voltage 2
6.000V~9.999V
AD-04
AI2 measured voltage 1
0.500V~4.000V
AD-05
AI2 display voltage 1
0.500V~4.000V
AD-06
AI2 measured voltage 2
6.000V~9.999V
AD-07
AI2 display voltage 2
6.000V~9.999V
AD-08
AI3 measured voltage 1 (only AI3
support negative voltage)
-9.999V~9.999V
VH6
VB5N
Modbus address
Function
Modbus address
Function
1000H
Communication frequency
2001H
Communication frequency
1100H
1: Forward running
2: Reverse operation
3: Forward jog
4: Reverse jog
5: Deceleration stop
6: Free stop
7: Fault reset
2000H
01H:Running command
02H:Forward command
03H:Reverse command
04H:Jog command(forward)
05H:Jog forward command
06H:Jog reverse command
07H:Decelerate stop command
08H:Emergency stop command
09H:Jog stop command
0AH:Fault reset command

Table of Contents