50
4. Function parameters
4-1. Function code list
‘○’: Parameters can be modified during operation.
‘×’: Parameters cannot be modified during operation.
‘—‘: Read only, user cannot change.
Group P0: Basic operation parameters
Group P0: Basic operation parameters
Parameter
Name
Setting range
Default
value
Modify
Modbus
address
P0-01
First motor control mode
0: VF control mode
1: No speed sensor vector control (SVC)
2: Vector control with speed sensor ( FVC)
0 (VH6)
1 (VH6S)
×
0001H
P0-02
Operation command channel
selection
0: Operation panel
1: Terminal operation
2: Communication port
0
0002H
P0-03
Main frequency source A
channel selection
0: Digital setting (Power-off no memory)
1: Digital setting (Power-off memory)
2: AI1
3: AI2
4: AI3
5: Terminal pulse X4 setting
6: Communication setting
7: Multi-segment command setting
8: PID setting
9: Simple PLC operation
10:Specific mode for wire drawing and winding
(supported by 3720 and above versions)
11:Panel knob setting(supported by LED panel
with knob, 3730 and above versions)
0
×
0003H
P0-04
Auxiliary frequency source B
channel selection
0: Digital setting (no memory when power off)
1: Digital setting (power down memory)
2: AI1
3: AI2
4: AI3
5: Terminal pulse X4 setting
6: Communication setting
7: Multi-segment command setting
8: PID setting
9: Simple PLC operation
10:Specific mode for wire drawing and winding
(supported by 3720 and above versions)
11:Panel knob setting(supported by LED panel
with knob, 3730 and above versions)
0
×
0004H