Group P3: Output terminal function parameters
Group P3: Output terminal function parameters
Parameter
Name
Setting range
Default
value
Modify
Modbus
address
P3-00
Y2 output mode
0: High speed pulse output
1: Common terminal output
0
0300H
P3-01
Y1 output function
selection
0: No output
1: Inverter in operation
2: Fault output (free stop fault)
3: Frequency level detection FDT1 output
4: Frequency level detection FDT2 output
5: Frequency arrival
6: Zero speed operation (no output during
shutdown)
7: Zero speed operation 2 (output when
shutdown)
8: Upper limit frequency arrival
9:Lower limit frequency arrival (operation
related)
10: Motor overload alarm
11: Frequency converter overload alarm
12: Communication settings
13: In torque limit
15: Frequency 1 reached output
16: Frequency 2 reached output
17: Current 1 reached output
18: Current 2 reached output
19: Set counting value reached
20: Specified counting value reached
21: Ready for operation
23: AI1 input overrange
24: Under voltage state output
25: Cumulative power on time reached
26: Timing arrival output
27: Length arrived
28: Simple PLC cycle completed
29: Cumulative running time arrival
32: Lower limit frequency reached (output when
shutdown)
33: Fault output (free stop fault and no output
under voltage)
34: Module temperature reached
35: Warning output (all faults)
37: In reverse operation
39: Output current overrange
40: Zero current state
41: This time of running time arrived
42: Bus voltage reaches
01
0301H
P3-02
Y2 (normal terminal)
output function selection
00
0302H
P3-04
Relay 1 output function
selection
02
0304H
P3-05
Relay 2 output function
selection
00
0305H
P3-06
Y1 output delay time
0.0s~3600.0s
0.0s
0306H
P3-07
Y2 (normal terminal)
0.0s~3600.0s
0.0s
0307H