16
Power level
Installation spacing
0.7KW~15KW
A≥50MM
B≥10MM
C≥100MM
18.5KW~22KW
A≥50MM
B≥10MM
C≥200MM
22KW~37KW
A≥50MM
B≥50MM
C≥200MM
37KW~110KW
A≥50MM
B≥50MM
C≥300MM
2-1-4. Multiple installation
A
A
C
C
B B
D
Note:The installation dimensions at the positions of installing multiple frequency converters A, B and C are the
same as that of installing multiple single frequency converters. The installation spacing D between multiple
frequency converters is shown in the table below.
Power level
Installation spacing
3.7KW~15KW
D≥10MM
18.5KW~22KW
D≥10MM
22KW~37KW
D≥50MM
37KW~110KW
D≥50MM