39
Example of communication parameter setting:
Parameter
Name
Setting value
Note
P0-02
Operation command
channel
2
Communication command
P9-00
Communication
protocol selection
0
Modbus-RTU
P9-01
Local address
1
Station number 1
P9-02
Baud rate
6
19200BPS
P9-03
Data format
1
8-E-1
3-3-2. Start mode
There are three starting modes of frequency converter, which are direct starting, speed tracking restart and
asynchronous machine pre-excitation starting. They are selected by function parameter P4-00.
3-3-2-1. Direct start
Parameter
Name
Setting
value
Note
P4-00
Start mode
0
Direct start mode is applicable to most small inertia loads. The frequency
curve of start-up process is shown in the following figure. The "DC
braking" function before startup is applicable to the driving of elevator
and heavy load; the starting frequency is applicable to the equipment
which needs to impact start, such as cement mixer equipment.