Group P3: Output terminal function parameters
Parameter
Name
Setting range
Default
value
Modify
Modbus
address
output delay time
P3-09
Relay 1 output delay time
0.0s~3600.0s
0.0s
0309H
P3-10
Relay 2 output delay time
0.0s~3600.0s
0.0s
030AH
P3-11
Y terminal effective state
selection
0: positive logic
1: negative logic
Ones bit: Y1
Tens bit: Y2
Thousands bit: relay 1
Ten thousands bit: relay 2
00000
030BH
P3-12
Y2 (high speed pulse )
output selection
0: Operating frequency
1: Set frequency
2: Output current
3: Motor output torque (absolute value,
percentage relative to motor)
4: Output power
5: Output voltage
6: AI1
7: AI2
8: AI3
9: PULSE input (100.0% corresponding to
100.0KHz)
10: Output speed
11: Communication control output
12: Count value
13: Length
00
030CH
P3-13
AO1 output selection
00
030DH
P3-14
AO2 output selection
01
030EH
P3-15
AO1 zero bias coefficient
-100.0%~+100.0%
0.0%
030FH
P3-16
AO1 gain
-10.00~+10.00
1.00
0310H
P3-17
AO2 zero bias coefficient
-100.0%~+100.0%
0.0%
0311H
P3-18
AO2 gain
-10.00~+10.00
1.00
0312H
P3-23
Y2 (high speed pulse)
max input pulse
frequency
0.01KHz~50.0KHz
50.0KHz
0317H