23
(2)
Terminal description of control circuit
Type
Terminal
Name
Description
Communication
485+
485-
RS485 terminal
Standard RS485 communication interface, using twisted pair or
shielded wire.
Power supply
10V-GND
+10V power supply
External + 10V power supply, maximum output current: 20mA.
Generally used for external potentiometer speed regulation.
24V-0V
DC 24V power
supply
Provide + 24V power supply for terminal, maximum output
current: 100 mA
It is generally used as working power supply for digital input and
output terminals.
External load is not allowed to connect.
Common
terminal
COM
Common terminal
of input X
When using the internal power supply to drive the X terminal:
COM and 24V are short circuited to form NPN input;
COM and 0V are short circuited to form PNP input;
When using the external 24V power supply to drive the X
terminal:
COM is connected to external power supply 24V+, disconnected
from 24V of VH6 to form NPN input;
COM is connected to external power supply 0V, disconnected
from 0V of VH6 to form PNP input;
Analog input
AI1-GND
AI1
Select voltage /current input by DIP switch
Input voltage range: 0~10V (Input impedance: 22kΩ)
Input current range: 0~20mA (Input impedance: 500Ω)
AI2-GND
AI2
Analog output
AO1-GND
AO1
Select voltage/current output by DIP switch
Voltage output range: 0~10V. External load: 2kΩ-1MΩ
Current output range: 0~20mA. External load less than 500Ω
Digital input
X1
Input terminal 1
Optocoupler isolation input
Input impedance: R = 3.3KΩ
The input voltage range is 9 ~ 30V
Compatible with bipolar input
X2
Input terminal 2
X3
Input terminal 3
X4
Input terminal 4
In addition to the characteristics of X1-X3, it can also be used
as a high-speed pulse input channel. The highest frequency is 50
kHz
Digital output
Y1
Digital output
terminal 1
Collector open circuit output
Output voltage range: 0 ~ 24V
Output current range: 0 ~ 50mA
Relay output
TA1 TB1 TC1
Output relay 1
Programmable is defined as a variety of electrical output terminals
TA-TB: normally open
TA-TC: normally closed
Contactor capacity:
AC250V/2A (COSΦ=1)
AC250V/1A (COSΦ=0.4)
DC30V/1A