Xtreme Power Conversion Corporaon
TX90 6kVA & 10kVA Service Manual
Page 11
Uninterrupble Power Supply
L11 NOT USED: all systems are single input
N1, L12, G1: the terminals for ulity input with single input connecon
G1: the terminal for UPS input ground
N1: line 1 (L1) input
L12: line 2 (L2) input
G2, N22, L22, N21, L23, L21: the terminals for UPS output, see below output opons for conguraon details
G2: the terminal for UPS output ground
Remarks:
1. The maximum current for each terminal is 30 Amps for 6 kVA, 50 Amps for 10 kVA.
2. The UPS is always a Single Input conguraon. The Dual Input conguraon is not used. The AC source can
be 208V or 240V landed to the L12 and N1 terminals.
3. Use No. 6 AWG, 75°C minimum copper wire and 23 lb-in Torque force when connecng to terminal block.
4. The transformer has two input voltage opons, 208V and 240V. If the input is congured at 208V but the
actual input is 240V, then the output voltages will boost up 15%.
Input Conguraon
208V input applicaons: 208V input with a 120/240V output is the default for these systems. This means the in-
verter output is programmed to 208V and the output transformer primary tap is set to the 208V seng. These are
the default sengs for this system. Please refer to output Opon 1 in this secon.
240V input applicaons: If the input voltage is 240V, the following steps must be performed to obtain a 120/240V
output with a 240V input.
1. With no AC applied to the unit, change the transformer primary tap from 208V default seng to 240V
shown below. Access to tap sengs is gained by removing the side covers.
TX90-6K Input Taps TX90-10K Input Tap Board
2. The UPS inverter output voltage must also be programmed to 240V. Refer to the Changing the UPS Default
Sengs secon for more details. Opon 1 below provides a 120/240V output with a 240V input.
Move red
wire to here
when there is
a 240V input
Tap shown
on the 208V
seng
240V tap