oPE05
Run Command Selection Error
The Run command selection parameter b1-02 is set to 3 but
no option unit is installed.
Cause Possible Solutions
Frequency reference is assigned to an option unit (b1-01 =
2) that is not connected to the drive.
Reconnect the option unit to the drive.
Frequency reference is assigned to a potentiometer (b1-01
= 3) that is not connected to the drive.
The Run command is assigned to an option unit (b1-02 = 2)
that is not connected to the drive.
LED Operator Display Error Name
oPE10
V/f Data Setting Error
The following setting errors have occurred where: E1-04
is greater than or equal to E1-06
is greater than or equal to
E1-07 is greater than or equal to E1-09.
Cause Possible Solutions
Correct the settings for E1-04, -06, -07 and -09.
LED Operator Display Error Name
oPE11
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
Cause Possible Solutions
The following simultaneous contradictory settings: C6-05
is greater than 6 and C6-04 is greater than C6-03 (carrier
frequency lower limit is greater than the upper limit). If
C6-05 is less than or equal to
6, the drive operates at C6-03.
Correct the parameter settings.
Upper and lower limits between C6-02 and C6-05 contradict
each other.
5.6 Operator Programming Errors
140
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual