Single-Phase 200 V Three-Phase 200 V Three-Phase 400 V
Model
(Capacity)
Carrier
Frequency
(kHz)
Output
Current
(A)
Model
(Capacity)
Carrier
Frequency
(kHz)
Output
Current
(A)
Model
(Capacity)
Carrier
Frequency
(kHz)
Output
Current
(A)
BA0003
0.75 kW/
0.4 kW
2 3.3
2A0004
0.75 kW/
0.4 kW
2 3.3
4A0002
0.75 kW/
0.4 kW
2 2.1
10 3.0 10 3.0 8 1.8
15 2.4 15 2.4 15 1.1
BA0006
1.1 kW/
0.75 kW
2 6.0
— — —
4A0004
1.5 kW/
0.75 kW
2 4.1
10 5.0 8 3.4
15 4.0 15 2.0
— — —
2A0006
1.1 kW/
0.75W
2 6.0
— — —10 5.0
15 4.0
— — —
2A0008
1.5 kW/
1.1 kW
2 8.0
— — —8 6.9
15 5.5
BA0010
2.2 kW/
1.5W
2 9.6
2A0010
2.2 kW/
1.5W
2 9.6
4A0005
2.2 kW/
1.5W
2 5.4
8 8.0 8 8.0 8 4.8
15 6.4 15 6.4 15 2.9
— — —
2A0012
3.0 kW/
2.2 kW
2 12.0
4A0007
3.0 kW/
2.2 kW
2 6.9
8 11.0 8 5.5
15 8.8 15 3.3
— — —
2A0018
3.7 kW/
3.0W
2 17.5
4A0009
3.7 kW/
3.0 kW
2 8.8
8 14.0 8 7.2
15 11.2 15 4.3
— — —
2A0020
5.5 kW/
4.0 kW
2 19.6
4A0011
5.5 kW/
4.0 kW
2 11.1
8 17.5 8 9.2
15 14.0 15 5.5
u
Multi-Step Speed Operation (4-Step Speed)
Select up to 9 preset references (including Jog reference) using two multi-function inputs S4
and S5. Two multi-step references can be selected using two multi-function inputs as
illustrated in Figure 4.14.
n
Multi-Step Speed Operation Parameters
No. Name Description
d1-01 Frequency Reference 1 Frequency reference. o1-03 determines the units, with Hz as the default.
d1-02 Frequency Reference 2
Frequency reference when multi-function input “Multi-Step Speed Reference
1" (H1-oo = 3) is on. Setting unit: set by o1-03.
d1-03 Frequency Reference 3
Frequency reference when multi-function input “Multi-Step Speed Reference
2” (H1-oo = 4) is on. Setting unit: set by o1-03.
4.5 Basic Operation
96
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual