B.3 Defaults Determined by Drive Capacity
(o2-04) and ND/HD (C6-01)
Table B.1 Single-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD Settings
No. Description Unit Default Settings
Model CIMR-Jo
BA0001 BA0002 BA0003
C6-01 Normal/Heavy Duty HD ND HD ND HD ND
o2-04 Drive Model Selection Hex 30 31 32
Motor rated power kW 0.1 0.2 0.2 0.4 0.4 0.75
C6-02 Carrier frequency 4 7 4 7 4 7
E2-01 Motor rated current A 0.60 1.10 1.10 1.90 1.90 3.30
E2-02 Motor rated slip Hz 2.50 2.60 2.60 2.90 2.90 2.50
E2-03 Motor no-load current A 0.40 0.80 0.80 1.20 1.20 1.80
E2-05 Motor line-to-line resistance Ω 35.98 20.56 20.56 9.842 9.842 5.156
Momentary power loss ride-
through time
s 0.1 0.1 0.1 0.1 0.1 0.1
Mom. power loss Baseblock
time
s 0.2 0.2 0.2 0.2 0.2 0.3
No. Description Unit Default Settings
Model CIMR-Jo
BA0006 BA0010
C6-01 Normal/Heavy Duty HD HD ND
o2-04 Drive Model Selection Hex 33 34
C6-02 Carrier frequency 4 7 3 7
E2-01 Motor rated current A 3.30 6.20 6.20 8.50
E2-02 Motor rated slip Hz 2.50 2.60 2.60 2.90
E2-03 Motor no-load current A 1.80 2.80 2.80 3.00
E2-05 Motor line-to-line resistance Ω 5.156 1.997 1.997 1.601
Momentary power loss ride-through time s 0.2 0.2 0.3 0.3
Momentary power loss Baseblock time s 0.3 0.4 0.4 0.5
Table B.2 Three-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD settings
No. Description Unit Default Settings
Model CIMR-Jo
2A0001 2A0002 2A0004 2A0006 2A0008
C6-01 Normal/Heavy Duty HD ND HD ND HD ND HD ND HD ND
o2-04 Drive Model Selection 96 (60H) 97 (61H) 98 (62H) 99 (63H) 100 (64H)
Motor rated power kW 0.1 0.2 0.2 0.4 0.4 0.75 0.75 1.1 1.1 1.5
C6-02 Carrier frequency 4 7 4 7 4 7 4 7 3 7
E2-01 Motor rated current A 0.60 1.10 1.10 1.90 1.90 3.30 3.30 4.90 4.90 6.20
E2-02 Motor rated slip Hz 2.50 2.60 2.60 2.90 2.90 2.50 2.50 2.60 2.60 2.60
E2-03 Motor no-load current A 0.40 0.80 0.80 1.20 1.20 1.80 1.80 2.30 2.30 2.80
E2-05
Motor line-to-line
resistance
Ω 35.98 20.56 20.56 9.842 9.842 5.156 5.156 3.577 3.577 1.997
L2-02
Momentary power loss ride-
through time
s 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.3
B.3 Defaults Determined by Drive Capacity (o2-04) and ND/HD (C6-01)
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
219
B
Parameter List
2/6/2008-14:44

Table of Contents

Related product manuals