B.2 Parameter Table
u
A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the
parameter Access Level, and Password.
No. Name Description Range Def.
Mode
Addr.
Hex
Pg.
V/f
A1: Initialization Parameters
Use A1 parameters to configure the basic environment for drive operation.
A1-01
<22>
Access Level
Selection
Selects which parameters are accessible via the digital
operator.
0: Operation only
2: Advanced Access Level
0, 2 2 O 101 116
A1-03
Initialize
Parameters
Resets all parameters to factory default settings.
(Initializes the drive then returns A1-03 to 0)
0: No Initialize
2220: 2-Wire Initialization
3330: 3-Wire Initialization
0 to
3330
0 O 103 87
U2 monitors are not reset when
performing initialization.
A1-04 Password 1
When the value set into A1-04 does not match the
value set into A1-05, parameters A1-01 and A1-03
cannot be changed.
0 to
9999
0 O 104 116
A1-05 Password 2
0 to
9999
0 O 105 116
This parameter is hidden from view. To
access A1-05, first display A1-04. Then
press the
STOP key while holding down
the up arrow key. Parameter A1-05 will
appear.
<22> Parameter can be changed during run.
u
b: Application
Application parameters configure the Run Command Source, DC Injection Braking, and other
application-related settings.
No. Name Description Range Def.
Mode
Addr.
Hex
Pg.
V/f
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
b1-01
Frequency
Reference
Selection
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal
2: MEMOBUS/Modbus communications (option)
3: Potentiometer (option)
0 to 3 1 S 180 87
b1-02
Run Command
Selection
Selects the run command input source.
0: Operator - RUN and STOP keys on the digital
operator
1: Digital input terminals
2: MEMOBUS/Modbus communications (option)
0 to 2 1 S 181 89
B.2 Parameter Table
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
199
B
Parameter List