EasyManua.ls Logo

YASKAWA GA800 Series - Safe Disable Function Notes and Warnings

YASKAWA GA800 Series
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.6 Control I/O Connections
104 YASKAWA SIEPC71061737B GA800 Drive Technical Reference
Terminal Input Signal
DIP Switch Settings Parameter
Switch Setting No. Signal Level
A3
Voltage input
S1-3
V
(Default)
H3-05
0: 0 V to 10 V/0% to 100% (input impedance: 20 kΩ)
1: -10 V to +10 V/-100% to 100% (input impedance: 20 kΩ)
Current input I
2: 4 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
3: 0 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
Note:
Set H3-02, H3-10 = 0 [Terminal A1 Function Selection, Terminal A2 Function Selection = Frequency Reference] to set A1 and A2 to
frequency reference. The drive will add the analog input values together to make the frequency reference.
Use tweezers or a jig with a tip width of approximately 0.8 mm (0.03 in) to set DIP switches.
Set DIP switch S4 to AI to use terminal A3 as an analog input (voltage/current) terminal. The default setting for DIP switch S4 is AI.
Set MFAI Terminal A3 to PTC Input
Set terminal A3 as an MFAI or as the PTC input for motor overload protection.
Use DIP switch S4 to set the input function.
Figure 3.50 Location of DIP Switch S4
Terminal Settings for DIP Switches Description
A3
AI
(Default)
Functions as an MFAI terminal.
Set H3-06 [Terminal A3 Function Selection] to select the input function.
PTC
Functions as the PTC input terminal.
Set H3-06 = E [Motor Temperature (PTC Input)].
Set S1-3 to V for voltage input.
Set Output Signals for MFAO Terminals FM, AM
Set the signal type for terminals AM and FM to voltage or current output. Use jumper switch S5 and H4-07, H4-08
[Terminal FM Signal Level Select, Terminal AM Signal Level Select] to set the signal type.
Figure 3.51 Location of Jumper Switch S5

Table of Contents

Other manuals for YASKAWA GA800 Series

Related product manuals