EasyManua.ls Logo

YASKAWA GA800 Series - Wire Gauge and Torque Specs for UL Listing (400 V Class)

YASKAWA GA800 Series
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mechanical Installation
2
2.3 Installation Position and Distance
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 35
2.3 Installation Position and Distance
Install the drive vertically for sufficient airflow to cool the drive.
Note:
Contact Yaskawa or a Yaskawa representative for more information about installing drive models on their side.
A - Vertical installation B - Horizontal installation
Figure 2.1 Installation Orientation
Single Drive Installation
Use the clearances specified in Figure 2.2 to install the drive. Make sure that there is sufficient space for wiring and
airflow to cool the drive.
A - 50 mm (2 in) minimum
B - 30 mm (1.2 in) minimum on both
sides
C - 120 mm (4.7 in) minimum above
and below
D - Airflow direction
Figure 2.2 Installation Distances for One Drive
Install Drives Side-by-Side
Users can install drive models 2004xB to 2082xB and 4002xB to 4044xB side-by-side.
When you install other drives side-by-side, keep the space that is sufficient for single drive installation between the
drives.
Side-by-side installation requires the installation space shown in Figure 2.3. Set L8-35 = 1 [Installation Method
Selection = Side-by-Side Mounting].
With reference to Derating Depending on Ambient Temperature on page 450, set derating depending on ambient
temperature.

Table of Contents

Other manuals for YASKAWA GA800 Series