4.6 Keypad Operation
166 YASKAWA SIEPC71061737B GA800 Drive Technical Reference
Save a Backup of Parameters
You can save a backup of the drive parameters to the keypad. The keypad can store parameter setting values for a
maximum of four drives in different storage areas. Parameter setting backups can save time when you set parameters
after you replace a drive. If you set up more than one drive, you can copy the parameter settings from a drive that
completed a test run to the other drives.
Note:
Stop the motor before you back up parameters.
While you back up parameters, the drive will not accept Run commands.
The DriveWorksEZ PC software password is necessary to back up qx-xx [DriveWorksEZ Parameters] and rx-xx [DWEZ Connection
Parameters]. If you enter an incorrect password, the drive detects PWEr [DWEZ Password Missmatch].
1. Push (Home) to show the HOME screen.
Note:
When the drive is in HOME Mode, the screen shows [Home] in the upper right-hand corner of the screen.
If the screen does not show [Home] for , push (Back), and then push to show [Home].
2. Push (Menu).
3. Push or to select [Parameter Backup/Restore], then push .
4. Push or to select the items to back up, then push .
5. Push or to select [Backup (drive keypad)], then push .