2.9 Installation Methods
52 YASKAWA SIEPC71061737B GA800 Drive Technical Reference
2.9 Installation Methods
The drive installation methods include standard installation and external heatsink installation.
Standard Installation
Refer to Drive Exterior and Mounting Dimensions on page 452 for more information about external dimensions and
installation methods.
External Heatsink Installation
Table 2.8, Table 2.9, and Table 2.10 show the panel cut-out dimensions for external heatsink installations. An
attachment is necessary to install drive models smaller than 2082 (200 V class) and 4060 (400 V class) with the
heatsink outside of the panel.
Note:
The exterior mounting dimensions and installation dimensions for a standard installation are different than the dimensions for an external
heatsink installation.
The shaded parts of the panel cut-out dimensions are the gasket dimensions. Make sure that the gasket is not smaller than the specified
dimension.
Table 2.7 External Heatsink Installation Kit
Drive Model Model
2004 to 2042
4002 to 4023
900-193-209-001
2056
4031, 4038
900-193-209-002
2070, 2082
4044, 4060
900-193-209-003
2110 to 2415
4075 to 4720
-