3.4 Main Circuit Terminal Block Wiring Procedure
86 YASKAWA SIEPC71061737B GA800 Drive Technical Reference
3.4 Main Circuit Terminal Block Wiring Procedure
DANGER! Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before servicing,
disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal capacitor
stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage decreases below 50
Vdc. When all indicators are OFF, remove the covers before measuring for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock. The drive has internal
capacitors that stay charged after you de-energize the drive.
The procedures to wire the main circuit terminal block are different for different drive models. Refer to Table 3.4 for
procedures by drive model.
Table 3.4 Types of Wiring Procedure for the Main Circuit Terminal Block
Model Procedure Reference
2004 - 2211
4002 - 4168
Procedure A 86
2257 - 2415
4208 - 4720
Procedure B 90
Wire the Main Circuit Terminal Block with Procedure A
Notes on Wiring the Main Circuit Terminal Block
Read these notes before you wire the main circuit terminal block.