Standards Compliance
5
5.3 UL Standards
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 251
Drive Model
Semiconductor Fuse
Manufacturer: EATON/Bussmann
Alternate Time-Delay
Class CC, J, or T
*1
Maximum Amp Rating
(Maximum SCCR (kA))
4007 FWH-60B 12 (100)
4009 FWH-60B 15 (100)
4012 FWH-60B 20 (100)
4018 FWH-80B 30 (100)
4023 FWH-90B 40 (100)
4031 FWH-150B 50 (100)
4038 FWH-200B 60 (100)
4044 FWH-200B 70 (100)
4060 FWH-225A 100 (100)
4075 FWH-250A 125 (100)
4089 FWH-275A 150 (100)
4103 FWH-275A 175 (100)
4140 FWH-300A 225 (100)
4168
FWH-325A
FWH-400A
*2
250 (100)
4208 FWH-500A 350 (100)
4250 FWH-600A 400 (100)
4302 FWH-700A 500 (100)
4371 FWH-800A Not applicable
4414 FWH-1000A Not applicable
4477 FWH-1200A Not applicable
4568 FWH-1200A Not applicable
4605 FWH-1400A Not applicable
4720 FWH-1400A Not applicable
*1 Class T fuses are fast-acting (non-time delay only).
*2 Yaskawa recommends a fuse with a larger rated current for cyclical load applications that frequently approach 150 % overload.
UL Standards Compliance for DC Power Supply Input
To comply with UL Standards, install a fuse for the DC power supply input.
Figure 5.11 shows a wiring example for a DC power supply that has two drives connected in parallel.
Figure 5.11 Wiring Example for DC Power Supply Input
WARNING! Electrical Shock Hazard. Do not ground the main circuit bus. Incorrect wiring can cause serious injury or death.