2.3 Installation Position and Distance
36 YASKAWA SIEPC71061737B GA800 Drive Technical Reference
A - 50 mm (2 in) minimum
B - 30 mm (1.2 in) minimum on both
sides
C - 2 mm (0.08 in) minimum between
each drive
D - 120 mm (4.7 in) minimum above
and below
Figure 2.3 Installation Distances for Multiple Drives (Side-by-Side)
Note:
• Align the tops of drives that have different dimensions to help when you replace cooling fans.
• Remove the top protective covers of all drives when mounting UL Type 1 enclosure drives side-by-side.
Figure 2.4 Enclosed Wall-Mounted Type (UL Type 1) Installed Side-by-Side