5.3 UL Standards
254 YASKAWA SIEPC71061737B GA800 Drive Technical Reference
■ E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E2-01
(030E)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Note:
• If E2-01 < E2-03 [Motor No-Load Current], the drive will detect oPE02 [Parameter Range Setting Error].
• When the drive model changes, the display units for this parameter also change.
–0.01 A: models 2004 to 2042, 4002 to 4023
–0.1 A: models 2056 to 2415, 4031 to 4720
The value set for E2-01 becomes the reference value for motor protection, the torque limit, and torque control. Enter
the motor rated current shown on the motor nameplate. Auto-Tuning the drive will automatically set E2-01 to the
value input for “Motor Rated Current”.
■ E5-03: PM Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E5-03
(032B)
PM Motor Rated Current
(FLA)
Sets the PM motor rated current (FLA).
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
• 0.01 A: models 2004 to 2042, 4002 to 4023
• 0.1 A: models 2056 to 2415, 4031 to 4720
After you do these types of Auto-Tuning, the drive automatically will set E5-03 to the value input for “PM Motor
Rated Current”:
• PM Motor Parameter Settings
• PM Stationary Auto-Tuning
• PM StaTun for Stator Resistance
• PM Rotational Auto-Tuning
■ E9-06: Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E9-06
(11E9)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by E9-01 and
o2-04
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
• 0.01 A: models 2004 to 2042, 4002 to 4023
• 0.1 A: models 2056 to 2415, 4031 to 4720
The value set for E9-06 becomes the reference value for motor protection. Enter the motor rated current shown on the
motor nameplate. Auto-Tuning the drive will automatically set E9-06 to the value input for “Motor Rated Current”.
■ L1-01: Motor Overload (oL1) Protection
No.
(Hex.)
Name Description
Default
(Range)
L1-01
(0480)
Motor Overload (oL1)
Protection
Sets the motor overload protection with electronic thermal protectors.
Determined by A1-02
(0 - 6)
This parameter enables and disables the motor overload protection with electronic thermal protectors.