EasyManua.ls Logo

YASKAWA GA800 Series - Page 327

YASKAWA GA800 Series
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
7
7.4 Fault
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 327
Code Name Causes Possible Solutions
oFA10, oFA11
Option Card Error Occurred at
Option Port CN5-A
A fault occurred in the option card. 1. De-energize the drive.
2. Make sure that the option card is correctly connected to the
connector.
3. If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
oFA12 to
oFA17
Option Card Connection Error (CN5-
A)
A fault occurred in the option card. 1. De-energize the drive.
2. Make sure that the option card is correctly connected to the
connector.
3. If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
oFA30 to
oFA43
Communication Option Card
Connection Error (CN5-A)
A fault occurred in the option card. 1. De-energize the drive.
2. Make sure that the option card is correctly connected to the
connector.
3. If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
oFb00 Option Not Compatible with Port
The option card connected to connector CN5-B is not
compatible.
Connect the option card to the correct connector.
Note:
DO-A3, AO-A3, PG-B3, and PG-X3 options can connect to
connector CN5-B. Use connector CN5-C when connecting only
one encoder option card.
Note:
Do a Fault Reset to clear the fault.
Fault trace is not available for this fault.
Code Name Causes Possible Solutions
oFb01 Option Fault/Connection Error
The option card connected to connector CN5-B was
changed during operation.
1. De-energize the drive.
2. Refer to the option card manual and correctly connect the
option card to the connector on the drive.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
oFb02 Duplicate Options
The same option cards or the same type of option
cards are connected to connectors CN5-A, B, and C.
Connect the option card to the correct connector.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
oFb03 to oFb11
Option Card Error Occurred at
Option Port CN5-B
A fault occurred in the option card. 1. De-energize the drive.
2. Make sure that the option card is correctly connected to the
connector.
3. If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
oFb12 to oFb17
Option Card Error Occurred at
Option Port CN5-B
A fault occurred in the option card. 1. De-energize the drive.
2. Make sure that the option card is correctly connected to the
connector.
3. If the problem continues, replace the option card.
Note:
Do a Fault Reset to clear the fault.