Parameter Details
12
12.3 b: Application
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 685
Figure 12.33 Example of How the Timer Function Works with H2-01 Terminals
Note:
When the terminal is triggered, it continues for a minimum of 100 ms. The on/off-delay time of MFDO terminal does not have an effect.
b4-01: Timer Function ON-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-01
(01A3)
Timer Function ON-Delay
Time
Sets the ON-delay time for the timer input.
0.0 s
(0.0 - 3000.0 s)
b4-02: Timer Function OFF-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-02
(01A4)
Timer Function OFF-Delay
Time
Sets the OFF-delay time for the timer input.
0.0 s
(0.0 - 3000.0 s)
b4-03: Terminal M1-M2 ON-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-03
(0B30)
Expert
Terminal M1-M2 ON-Delay
Time
Sets the delay time until the contact is turned ON after the function set with H2-01 turns ON.
0 ms
(0 - 65000 ms)
b4-04: Terminal M1-M2 OFF-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-04
(0B31)
Expert
Terminal M1-M2 OFF-Delay
Time
Sets the delay time to deactivate the contact after the function set in H2-01 deactivates.
0 ms
(0 - 65000 ms)
b4-05: Terminal M3-M4 ON-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-05
(0B32)
Expert
Terminal M3-M4 ON-Delay
Time
Sets the delay time to activate the contact after the function set in H2-02 activates.
0 ms
(0 - 65000 ms)
b4-06: Terminal M3-M4 OFF-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-06
(0B33)
Expert
Terminal M3-M4 OFF-Delay
Time
Sets the delay time to deactivate the contact after the function set in H2-02 deactivates.
0 ms
(0 - 65000 ms)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV