EasyManua.ls Logo

YASKAWA GA800 Series - Page 787

YASKAWA GA800 Series
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.7 F: Options
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 787
F1-37: Encoder 2 Signal Selection
No.
(Hex.)
Name Description
Default
(Range)
F1-37
(03BD)
Encoder 2 Signal Selection
Sets the number of channels for the signal to the encoder option card for motor 2.
0
(0, 1)
0 : A Pulse Detection
1 : AB Pulse Detection
F1-46: Deviation 2 Detection Method Selection
No.
(Hex.)
Name Description
Default
(Range)
F1-46
(1B98)
Deviation 2 Detection
Method Selection
Usually it is not necessary to change this setting. Sets the detection method for dv2 [Z Pulse Noise
Fault Detection].
0
(0, 1)
To detect dv2 while a multi-pole motor (for example 24 or more poles) is running at zero speed, set F1-46 = 1
[Mechanical Angle Detection Method].
0 : Electrical Angle Detection Method
1 : Mechanical Angle Detection Method
F1-47: Deviation 2 Detection Selection
No.
(Hex.)
Name Description
Default
(Range)
F1-47
(1B99)
Deviation 2 Detection
Selection
Usually it is not necessary to change this setting. Sets the sensitivity of detection for dv2 [Z Pulse
Noise Fault Detection]. Increase the value to decrease the sensitivity.
15°
(0 - 180°)
These F1-46 [dv2 Detection Method Selection] settings change the setting units of F1-47:
F1-46 = 0: F1-47 uses electric angles (deg)
F1-46 = 1: F1-47 uses mechanical angles (one motor rotation is equivalent to a mechanical angle of 360 degrees)
F1-50: PG-F3 Option Encoder Type
No.
(Hex.)
Name Description
Default
(Range)
F1-50
(03D2)
PG-F3 Option Encoder Type
Sets the type of encoder connected to the PG-F3 option.
0
(0 - 2)
0 : EnDat Sin/Cos
1 : EnDat Serial Only
2 : HIPERFACE
F1-51: PG-F3 PGoH Detection Level
No.
(Hex.)
Name Description
Default
(Range)
F1-51
(03D3)
PG-F3 PGoH Detection
Level
The drive will detect PGoH [Encoder (PG) Hardware Fault] if the value of this parameter is smaller
than the value of .
80%
(1 - 100%)
The drive will detect PGoH if the value of this parameter is smaller than the value of .
Regarding the expression , Sin θ is the single-track (phase B) output from the encoder and Cos θ is
the single-track (phase A) output from the encoder.
Note:
This function is enabled when F1-20 = 1 [Encoder 1 PCB Disconnect Detect = Enabled].
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800 Series

Related product manuals