EasyManua.ls Logo

YASKAWA GA800 Series - Page 791

YASKAWA GA800 Series
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.7 F: Options
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 791
F3-01: Digital Input Function Selection
No.
(Hex.)
Name Description
Default
(Range)
F3-01
(0390)
Digital Input Function
Selection
Sets the data format of digital input signals. This parameter is enabled when o1-03 = 0 or 1
[Frequency Display Unit Selection = 0.01 Hz or 0.01% (100% = E1-04)].
8
(0 - 8)
Note:
The input signal type is BCD when o1-03 = 2 or 3 [Revolutions Per Minute (RPM) or User Units (o1-10 & o1-11)]. The o1-03 value sets the
setting units.
0 : BCD, 1% units
1 : BCD, 0.1% units
2 : BCD, 0.01% units
3 : BCD, 1 Hz units
4 : BCD, 0.1 Hz units
5 : BCD, 0.01 Hz units
6 : BCD (5-digit), 0.01 Hz
7 : Binary input
The setting unit and setting range vary depending on the value set in F3-03 [Digital Input Data Length Select].
F3-03 = 0 [8-bit]: 100%/255 (-255 to +255)
F3-03 = 1 [12-bit]: 100%/4095 (-4095 to +4095)
F3-03 = 2 [16-bit]: 100%/30000 (-33000 to +33000)
8 : Multi-Function Digital Input
The DI-A3 card is also used as a multi-function digital input terminal.
F3-03: Digital Input Data Length Select
No.
(Hex.)
Name Description
Default
(Range)
F3-03
(03B9)
Digital Input Data Length
Select
Sets the number of bits to set the frequency reference with DI-A3.
2
(0 - 2)
0 : 8-bit
1 : 12-bit
2 : 16-bit
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800 Series

Related product manuals