EasyManua.ls Logo

YASKAWA GA800 Series - Page 805

YASKAWA GA800 Series
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.7 F: Options
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 805
Register
No. (Hex.)
Description
15EF
Slave Address for Reg. Access + During MEMOBUS process & ErrCode
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
00H: MEMOBUS/Modbus Communication Complete
02H: Register number not registered
21H: Upper/Lower Limit Fault
22H: Write Mode Error
23H: Write performed during Uv
24H: Write performed while writing parameter settings
FFH: During MEMOBUS/Modbus Communication
Note:
If you change the access command before the MEMOBUS/Modbus access flag turns on,
the drive will not do the command from before.
bit 8
bit 9
bit A
bit B
Slave address
0: MEMOBUS command ignored
1: Drive 1
2: Drive 2
3: Drive 3
4: Drive 4
5: Broadcast Messages (run command and frequency reference)
bit C - F Reserved
15F0 Register number
15F1 Data (write register)
F6-01: Communication Error Selection
No.
(Hex.)
Name Description
Default
(Range)
F6-01
(03A2)
Communication Error
Selection
Sets the method to stop the motor or let the motor continue operating when the drive detects a bUS
[Option Communication Error].
1
(0 - 5)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON, and MB-
MC turns OFF.
1 : Coast to Stop
The output turns off and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns
OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC
turns ON, and MB-MC turns OFF.
3 : Alarm Only
The keypad shows bUS and the drive continues operation at the current frequency reference.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
The output terminal set for Alarm [H2-01 to H2-03 = 10] activates.
4 : Alarm (Run at d1-04)
The keypad shows bUS and the drive continues operation at the speed set in d1-04 [Reference 4].
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
5 : Alarm - Ramp Stop
The drive stops the motor in the deceleration time set in C1-02 [Deceleration Time 1].
After you remove the bUS alarm, the motor will accelerate to the frequency reference you set before.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800 Series

Related product manuals