Parameter Details
12
12.8 H: Terminal Functions
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 849
H2-06: Watt Hour Output Unit Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-06
(0437)
Watt Hour Output Unit
Selection
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection = Watt
Hour Pulse Output].
0
(0 - 4)
This output is input to the Watt hour meter or PLC through a 200 ms pulse signal. This parameter sets the kWh unit
for each pulse output.
Figure 12.88 Example MFDO when Configured for Watt Hours
Note:
When the power value is a negative value (regenerative state), the drive does not count Watt hours.
When the control power supply to the drive is operating, the drive will keep the Watt hours. If a momentary power loss causes the drive to
lose control power, the Watt hour count will reset.
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
H2-07: Modbus Register 1 Address Select
No.
(Hex.)
Name Description
Default
(Range)
H2-07
(0B3A)
Modbus Register 1 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets the address of the register that is output to Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62] and uses the bit
in H2-08 [Modbus Register 1 Bit Select].
H2-08: Modbus Register 1 Bit Select
No.
(Hex.)
Name Description
Default
(Range)
H2-08
(0B3B)
Modbus Register 1 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
Sets the bit of the register that is output to Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62] and uses the address
in H2-07 [Modbus Register 1 Address Select].
H2-09: Modbus Register 2 Address Select
No.
(Hex.)
Name Description
Default
(Range)
H2-09
(0B3C)
Modbus Register 2 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets H2-09 with the address of the register that is output to Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63] and
uses the bit in H2-10 [Modbus Register 2 Bit Select].
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV