Parameter Details
12
12.8 H: Terminal Functions
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 851
H2-25: Comparator 1 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-25
(1545)
Comparator 1 Off-Delay
Time
Sets the off-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 869 and 67: Comparator2 on page 869.
H2-26: Comparator 2 Monitor Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-26
(1546)
Comparator 2 Monitor
Selection
Sets the monitor number for comparator 2. Set the x-xx part of the Ux-xx [Monitor]. For example, set
H2-26 = 103 to monitor U1-03 [Output Current].
103
(000 - 999)
Note:
The configurable monitor changes when the control method changes.
When you use the terminal in through mode, set this parameter to 000 or 031. You can set the terminal output level from the PLC through
MEMOBUS/Modbus communications or the communication option.
For information on the comparator function, refer to 66: Comparator1 on page 869 and 67: Comparator2 on page 869.
H2-27: Comparator 2 Lower Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-27
(1547)
Comparator 2 Lower Limit
Sets the lower limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 869 and 67: Comparator2 on page 869.
H2-28: Comparator 2 Upper Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-28
(1548)
Comparator 2 Upper Limit
Sets the upper limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 869 and 67: Comparator2 on page 869.
H2-29: Comparator 2 Hysteresis
No.
(Hex.)
Name Description
Default
(Range)
H2-29
(1549)
Comparator 2 Hysteresis
Sets the hysteresis level for comparator 2 as a percentage of the full scale analog output for the
monitor selected in H2-26 [Comparator 2 Monitor Selection].
0.0%
(0.0 - 10.0%)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 869 and 67: Comparator2 on page 869.
H2-30: Comparator 2 On-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-30
(154A)
Comparator 2 On-Delay
Time
Sets the on-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 869 and 67: Comparator2 on page 869.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800 Series

Related product manuals