EasyManua.ls Logo

YASKAWA GA800 Series - Page 856

YASKAWA GA800 Series
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.8 H: Terminal Functions
856 YASKAWA SIEPC71061737B GA800 Drive Technical Reference
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 Setting Control method selection Parameter Used as the Reference
0 V/f Control E1-09
1 V/f Control with Encoder E1-09
2 Open Loop Vector b2-01
3 Closed Loop Vector E1-09
4 Advanced OpenLoop Vector Control E1-09
5 PM Open Loop Vector E1-09
6 PM Advanced Open Loop Vector E1-09
7 PM Closed Loop Vector Control b2-01
8 EZ Open Loop Vector Control E1-09
Figure 12.90 Zero Speed Time Chart
ON : Output frequency < value of E1-09 or b2-01.
OFF : Output frequency value of E1-09 or b2-01.
2: Speed Agree 1
Setting Value Function Description
2 Speed Agree 1
The terminal turns on when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree Detection Width].
Note:
The detection function operates in the two motor rotation directions.
The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4 and n4-
72 = 1.
Figure 12.91 Speed Agree 1 Time Chart
ON : The output frequency is in the range of “frequency reference ± L4-02”.
OFF : The output frequency does not align with the frequency reference although the drive is
running.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800 Series

Related product manuals