12.11 o: Keypad-Related Settings
986 YASKAWA SIEPC71061737B GA800 Drive Technical Reference
o2-23: External 24V Powerloss Detection
No.
(Hex.)
Name Description
Default
(Setting Range)
o2-23
(11F8)
RUN
External 24V Powerloss
Detection
Sets the function to give a warning if the backup external 24 V power supply turns off when the main
circuit power supply is in operation.
0
(0, 1)
Note:
The drive will not run when it is operating from one 24-Vexternal power supply.
0 : Disabled
The drive does not detect the loss of the 24-V external power supply.
1 : Enabled
The keypad shows the L24v [Loss of External Power 24 Supply] indicator when the drive detects the loss of the 24-V
external power supply.
Note:
H2-xx = 10 [MFDO Function Selection = Minor Fault] will not output a minor fault signal.
o2-24: LED Light Function Selection
No.
(Hex.)
Name Description
Default
(Range)
o2-24
(11FE)
LED Light Function
Selection
Sets the function to show the LED status rings and keypad LED lamps.
2
(0 - 2)
Note:
When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will not reset this parameter.
0 : Enable Status Ring & Keypad LED
1 : LED Status Ring Disable
2 : Keypad LED Light Disable
o2-26: Alarm display at ext. 24V power
No.
(Hex.)
Name Description
Default
(Range)
o2-26
(1563)
Alarm display at ext. 24V
power
When you connect a backup external 24 V power supply, this parameter sets the function to trigger
an alarm when the main circuit power supply voltage decreases.
1
(0, 1)
0 : Disabled
The drive will not detect EP24v [External Power 24V Supply] if the main circuit power supply voltage decreases. The
[Ready] light on the LED Status Ring flashes quickly to identify that drive operation is not possible.
1 : Enabled
The drive detects EP24v when the main circuit power supply voltage decreases.
Note:
The minor fault signal is not output from H2-xx = 10 [MFDO Function Selection = Alarm].
o2-27: bCE Detection Selection
No.
(Hex.)
Name Description
Default
(Range)
o2-27
(1565)
bCE Detection Selection
Sets drive operation if the Bluetooth device is disconnected when you operate the drive in Bluetooth
Mode.
3
(0 - 4)
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents