n024
Frequency Frequency set by Digital Operator 0 to 400.0 0.0 (Hz) 5.19B
Reference 1 (or value retained by Up/Down or
See Note 4
(Reference 1) Sample/Hold function)
See Note 5
n025
Frequency Additional frequency setpoint for 0 to 400.0 0.0 (Hz) 5.19B
Reference 2 multi-step speed
See Note 4
(Reference 2)
n026
Frequency Additional frequency setpoint for 0 to 400.0 0.0 (Hz) 5.19B
Reference 3 multi-step speed
See Note 4
(Reference 3)
n027
Frequency Additional frequency setpoint for 0 to 400.0 0.0 (Hz) 5.19B
Reference 4 multi-step speed
See Note 4
(Reference 4)
n028
Frequency Additional frequency setpoint for 0 to 400.0 0.0 (Hz) 5.19B
Reference 5 multi-step speed
See Note 4
(Reference 5)
n029
Frequency Additional frequency setpoint for 0 to 400.0 0.0 (Hz) 5.19B
Reference 6 multi-step speed
See Note 4
(Reference 6)
n030
Jog Reference Operating frequency when a 0 to 400.0 6.0 (Hz) 5.15,
Jog command is input
See Note 4 5.19B
(Jog Reference)
n031
Frequency 0 to 109 100 (%) 5.12
Reference
Upper Limit
(Ref
Upper Limit)
n032
Frequency 0 to 100 0 (%) 5.12
Reference
Lower Limit
(Ref
Lower Limit)
n033
Motor Rated FLA rating of motor See Note 2 (A) 5.26
Current
(Motor Rated
See Note 3
FLA)
See Note 5
n034
Electronic LED LCD 0 to 4 1 5.26
Thermal Setting
Setting Characteristics
Overload 0 Disabled No protection
Protection 1
STD
Motor/8 min**
Standard motor (8 min.)
2 STD Motor/5 min Standard motor (5 min.)
(Motor OL Sel) 3 INV Motor/8 min Blower-cooled motor (8 min.)
4 INV Motor/5 min Blower-cooled motor (5 min.)
Table A1-1. Drive Parameters (
nXXX
) – Continued
PARAM.
FUNCTION NAME SETTING FACTORY USER PARA.
NO. (ACTUAL DISPLAY)
DESCRIPTION
RANGE SETTING ** SETTING REF.