n035
Overheat Stop LED LCD
Method Setting
Setting Stop method 0 to 3 3
0 Ramp STOP/Decel1 Ramp to stop –
(OH1 Stop Decel 1 (fault)
Method) 1 Coast to STOP Coast to stop (fault)
2 Ramp STOP/Decel1 Ramp to stop –
Decel 2 (fault)
3 Continue Oper** Continue operation (alarm)
at 80% & Freq. Ref.
n036
Multi-function LED LCD 0 to 28 0 5.19
Input Selection Setting
Setting
Description
0
Reverse RUN (2W)**
Reverse run ( 1 )*
(Terminal S2 (2-Wiresequence)
Sel)
[ can only be set in
n036
]
1 FWD/REV Cmd (3W) Fwd / Rev command
n037
Multi-function (3-Wire sequence) 2 to 28 2 5.19
Input Selection
[ can only be set in
n036
]
( – – ) *
[ When
n036
2 Ext Fault (NO) ** External fault (N.O.)
has been set 3 Ext Fault (NC) External fault (N.C.)
to " 1 ", this 4 Fault Reset ** Fault reset
parameter will 5 LOCAL/REMOTE SelRemote / Local selection
display “In Use 6 COM/INV Sel Serial communication/Dig.Op.
by Other”, and no (Freq. Ref. & Run command)
value can be 7 STOP Cmd/Dec2 NOStop command using Decel.
entered] Time 2 (Normally Open)
8 STOP Cmd/Dec2 NC Stop command using Decel.
(Terminal S3 Time 2 (Normally Closed)
Sel) 9 Master FREF Sel Auto frequency
reference selection
n038
Multi-function 10
Multi-Step Spd1**
Multi-step speed reference 2 to 28 4 5.19
Input Selection Command 1
11
Multi-Step Spd2**
Multi-step speed reference
(Terminal S4 Command 2
Sel) 12 Multi-Step Spd3 Multi-step speed reference
Command 3
n039
Multi-function 13 JOG Command Jog command 2 to 28 10 5.19
Input Selection 14 ACC/DEC Switch Accel/Decel time
[ When
n040
change command
has been set 15 Ext Baseblk (NO) External base block (N.O.)
to " 29 ", this 16 Ext Baseblk (NC) External base block (N.C.)
parameter will 17 SpdSrch (MAXFRQ) Speed search from
display " In Use maximum frequency
by Other” and no 18 SpdSrch (SETFRQ) Speed search from
value can be set frequency
entered] 19 Param Lockout Parameter change enable
20 PID I Reset I value reset (PID)
(Terminal S5
Sel) 21 PID Disable PID control of
Table A1-1. Drive Parameters (
nXXX
) – Continued
PARAM.
FUNCTION NAME SETTING FACTORY USER PARA.
NO. (ACTUAL DISPLAY)
DESCRIPTION
RANGE SETTING ** SETTING REF.